Display
- Two lines with 1.8" (46 mm) high digits, red LEDs; 6 digits per line (-99999 to 999999), with lead zero blanking
Display Intensity
- Eight user selectable intensity levels
Display Assignment
- Display lines 1 & 2 may be assigned to rate, total, grand total, alternate rate & total, max/min, units (lower display only), set points, Modbus input, & more.
Programming Methods
- Four programming buttons, digital inputs, PC and MeterView Pro software, or Modbus registers.
Noise Filter
- Programmable from 2 to 199 (0 will disable filter)
Filter Bypass
- Programmable from 0.1 to 99.9% of calibrated span
Recalibration
- All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Max/Min Display
- Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off
Password Restrict Modification
- Pass 3: Restricts all programming, function keys, and digital inputs
- Pass 2: Allows use of function keys, digital inputs and editing set/reset points
- Pass 1: Allows use of function keys and digital inputs
Power Options
- 12-24 VDC ± 10%, 15 W max. Powered over USB for configuration only
- 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
Isolated Transmitter Power Supply
- Terminals P+ & P-: 24 VDC ± 10%. 12-24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal P+/P- switch). 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
Non-Volatile Memory
- All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Fuse
- Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Normal Mode Rejection
- Greater than 60 dB at 50/60 Hz
Isolation
- 4 kV input/output-to-power line, 500 V input-to-output or output-to-P+ supply
Overvoltage Category
- Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III
Environmental
- Relative humidity: 0 to 90% non-condensing
- Operating Temperature Range: -40 to 150° F (-40 to 65° C)
- Storage Temperature Range: -40 to 185° F (-40 to 85° C)
Connections
- Removable and integrated screw terminal blocks accept 12 to 22 AWG wire
Enclosure
- UL Type 4X, IP65 rated. Polycarbonate & glass blended plastic case, color: gray. Includes four PG11 through-hole conduit openings, with two factory installed PG11, IP68, black nylon threaded hole plugs with backing nuts.
Wall Mounting
- Four (4) Mounting Holes Provided for Mounting Meter to Wall
Pipe Mounting
- Optional pipe mounting kit (PDA6260) allows for pipe mounting. Sold separately
Tightening Torque
- Digital I/O and RS485 Terminals: 2.2 lb-in (0.25 Nm)
- Removable Screw Terminals: 5 lb-in (0.56 Nm)
Overall Dimensions
- 10.63" x 12.59" x 4.77" (270 mm x 319.7 mm x 121.2 mm) (H x W x D)
UL File Number
- UL & C-UL Listed. E160849; 508 Industrial Control Equipment
USB Connection
- Cable: USB A Male to Micro-B Cable
- Connector Type: Micro-B receptacle
- Compatibility: USB 2.0 Standard, Compliant
- Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
- Power: USB Port